General information:

    • CT22-2CxOxC current transformer is molded by Huntsman’s plastic system with vacuum casting technology, has very good mechanical and electrical properties, withstands sudden temperature changes, CT22-2CxOxC current transformer Designed to suit tropical weather conditions and heavily polluted environments.
    • The CT22-2CxOxC current transformers are designed with one or more ratios, which can be changed by connecting the secondary side.
    • There are 2 secondary windings. The secondary winding is used for measurement or protection purposes. To prevent danger, the secondary circuit of the Current Transformer must always be connected to the load or short circuit. One terminal of the secondary winding shall be grounded during operation.
    • The current transformer can be installed in any position by the four bolts that go into the four holes on the base. The base is made of steel, solid structure and hot-dip galvanized, resistant to wet environments…
    • The outputs of the current transformers are molded to the body, the terminal cover has a cover and the sealing position.

Specifications:

    • Voltage levels…22, 24kV.
    • Rated primary current…5; ten; 15; 20; 25; 30; 40; 50; 60; 75; 100; 150; 200; 250; 300; 400; 500; 600; 750; 800; 1000; 1200A…
    • Rated secondary current…5A; 1A.
    • Rated frequency…50Hz.